China

雷竞技appFluke 707 ex Ann type circuit verification

  • 雷竞技appFluke 707 ex Ann type circuit verification
  • 雷竞技appFluke 707 ex Ann type circuit verification
Has been discontinued

The main features

  • Large display, the fast button interface, single hand operation
  • Shows percentage mA and reading at the same time, the measurement results can be quick, easy to read
  • Accuracy of 0.015% of the mA, is superior to other circuit verification
  • MA in the resolution of 1 (including A power supply, the simulation and measurement
  • Button control step value 25%, convenient linear detection
  • 0-100% span "check", a quick check zero and span
  • Optional slow, fast ramp, step function, providing continuous smooth output to test loop and slide valve
  • Provide 24 v circuit power supply, can give transmitter power supply, and to measure its output, need not carry DMMS
  • To measure up to 28 V dc voltage
  • Single section 9 V battery, easy to change
  • 0 to 20 mA, or 4 to 20 mA, the default boot mode
  • Innovation output adjustment dial, resolution 100 (including 1 (including A and A
  • HART ® compatible resistance and circuit switching power supply series, with HART communication equipment compatible
This product has been discontinued or reclassified

Produc雷竞技appts overview: Fluke 707 ex Ann type circuit verification

MA loop checking hand-held tool quickly

707 ex is for this Ann model loop checking instrument, can be used for the explosion danger area.雷竞技appFluke 707 ex经认证符合Zones 1 和 2下的ATEX指导(Ex II 2 G Eex ia IIC T4)。

Produc雷竞技appt specifications: Fluke 707 ex Ann type circuit verification

Technical indicators
Current measurement range 0 to 24 mA
The resolution of the 0.001 mA
precision Reading of 0.015% + 2 LSD
Output current range 0 to 20 mA, or 4 to 20 mA
precision Reading of 0.015% + 2 LSD
The drive ability 700 Ω 20 mA
Current simulation range 0 to 20 mA, or 4 to 20 mA
precision Reading of 0.015% + 2 LSD
Circuit power When measuring mA 24 V
Voltage measurement range 0 to 28 V dc
The resolution of the 1 mV
precision Reading of 0.015% + 2 LSD
Environmental indicators
Working temperature - 10 DHS to 55 DHS C C
Storage temperature - DHS 40 to 60 DHS C C
Humidity (no condensation) 0 to 95% in DHS (0 to 30 C DHS C);

0 to 75% (DHS 30 to 40 C DHS C)

0 to 45% (40 to 50 DHS C DHS C)

The temperature coefficient of - 10 to 18 DHS DHS C C, 28 DHS to 55 DHS C, C + / DHS C range is 0.005%
Safety specifications
security CSA C22.2 No. 1010.1, 1992
Electromagnetic compatibility (EMC) EN50082 - "92 and EN55022:1994 class B
Maximum voltage 30 V
ATEX certification The Ex II G Ex ia IIC T4 1 zone and 2 zone, ZELM 02 ATEX 0120 X
CE certification And EN61326 EN61010-1
The mechanical and general specifications
size 152 x 70 x 41 mm
The weight of the 224 g (350 g, including holster)
The battery Section 9 v alkaline battery
Warranty period 3 -
Shock and vibration According to MIL - T - 28800 (military specification) specification for level 2 meter
According to current and range ratio (%) There are
Automatic step, slope There are
Check the span There are

Mode雷竞技appl: Fluke 707 ex this type circuit verification

雷竞技appFluke 707 ex

The Ann model loop calibrator

  • Alligator clip
  • The operation manual (cd-rom version)
  • Protective cover, Flex - Stand ™
  • Safety design of the test line