雷竞技appFluke 6500-2 electrical safety tester
The main features
- Special keys, each completed tests can be "one key"
- Default pass/reject limit, to save time
- Wide bright backlit display, clear, easy to read
- Single power outlet for electrical connection
- Independent IEC socket, convenient and mains/extension tests
- Removable test line, but the scene quickly replaced
- Integrated handle
- USB port for data transmission
- Integrated QWERTY keyboard, input data quickly
- Attached to the USB memory for backup data storage and transmission to the PC
- Wide backlit graphical display
- The default, automatic test sequence, the convenient user use
- Integrated field, location and description coding, speed up the data processing
- Packet content view, help to achieve more on-site control function
- USB port for data transmission
Produc雷竞技appts overview: Fluke 6500-2 electrical safety tester
Perform more tests every day
雷竞技appFluke 6500-2 electrical safety tester is portable, compact one-click solution, the automatic testing function is redesigned, a day can help you finish more portable electrical test.Our aim in designing the 6500-2 is in does not affect the test results under the premise of to work faster.
One-click solution...
Just press a button, you can start the default test program.Not only simplify the test, and can achieve faster and more efficient way of working.6500-2 for fully automatic equipment, equipped with the user can define the test procedures and facilitate rapid QWERTY keyboard input data.
Light weight...
6500-2 weight is about 3 kg, light weight, easy to carry and convenient for field work.Rugged portable box (standard) can not only provide transportation protection, but also provide extra storage space, convenient store fittings and other tools.
Small volume...
The portable electric meter is very compact structure, and have fluke consistent durability, tailor-made for the job.雷竞技appFluke electrical safety tester is a complete integration solution, has the testing of portable electrical appliances all the required functions.
Produc雷竞技appt specifications: Fluke 6500-2 electrical safety tester
Technical indicators | ||
Test technical indicators | Display range of accuracy index defined as + + word reading (%), applicable to 23 ° C + 5 ° C and 75% RH or less. | |
0 ° C to 18 ° C and 28 ° C to 40 ° C, the accuracy of index every ° C reduces the accuracy index (0.1 x). | ||
Range accord with EN61557-1:1997, EN61557-2:1997, EN61557-4:1997, EN61557-6:1997, DIN VDE0404-2 specified in the service operation error. | ||
Electric test | Test instructions reverse L - N, lack of PE, and to measure the power supply voltage and frequency. | |
Display range | 90 V to 264 V | |
The accuracy of @ 50 Hz | 3 word plus or minus (+ 2%) | |
The resolution of the | 0.1 V | |
The input impedance | > 1 M Ω / 2.2 / nF | |
The maximum input voltage: | 264 V | |
Grounding connection test (Rpe) | Display range | Ω 0 to 19.99 |
Accuracy (grounding test after zero) | Plus or minus (+ 5%) 4 words | |
The resolution of the | 0.01 Ω | |
Test current | 200 mA AC - 0% + 40%, 1.99 Ω 10 A AC + / - 20%, 25 m Ω @ 230 V |
|
The open circuit voltage | > 4 V AC, < 24 V AC | |
Grounding test for zero | Maximum minus 1.99 Ω | |
Insulation test (Riso) | Display range | 0 to 299 M Ω |
The accuracy of | Plus or minus 5% (+ 2 word), 0.1 to 300 M Ω | |
The resolution of the | 0.01 M Ω (0 to 19.99 M Ω) 0.1 M Ω (20 to 199.9 M Ω) 1 M Ω (200-299 M Ω) |
|
The test voltage | 500 V DC - 0% + 25% @ 500 k Ω load, or 250 V DC - 0% + 25% @ 250 k Ω load | |
Test current | > 1 mA @ 500 k Ω load, < 15 mA @ 0 Ω | |
Automatic discharge time | U F < 0.5 s, 1 | |
The maximum load capacity | Operating up to 1 u F | |
Contact current test | Display range | 0 and 1.99 mA, AC |
The accuracy of | (plus or minus 4% + 2 words) | |
The resolution of the | 0.01 mA | |
The internal resistance (through probe) | 2 k Ω | |
Method of measurement | The probe * | |
Instead of leakage current test | Display range | 0 and 19.99 mA, AC |
The accuracy of | 3 word plus or minus (+ 2.5%) | |
The resolution of the | 0.01 mA | |
The test voltage | 100 V AC + / - 20% | |
Load/leakage test: load current | Display range | 0 A to 13 A |
The accuracy of | (plus or minus 4% + 2 words) | |
The resolution of the | 0.1 A * | |
Load/leakage current test, load power | Display range 230 V power supply | 0.0 VA to 3.2 kVA |
The accuracy of | 3 word plus or minus (+ 5%) | |
The resolution of the | VA VA) (0-999, 1 (> 1.0 kVA) * 0.1 kVA | |
Load/leakage current test: leakage current | Display range | 0 and 19.99 mA |
The accuracy of | Plus or minus (+ 4%) 4 words | |
The resolution of the | 0.01 mA * | |
PELV test | The accuracy of @ 50 Hz | 3 word plus or minus (+ 2%) |
Overload protection | 300 V RMS | |
The alarm threshold | 25 V RMS | |
RCD test: the tripping current | The operating error | Plus or minus 10% |
Nominal value | 30 mA | |
The accuracy of | Plus or minus 5% | |
RCD test: tripping time | Standard requirement | Chapter 6 61557;Rated test current tolerance of 0% to + 10% |
The operating error | Plus or minus 10% | |
RCD type | General 30 mA communication | |
Display range | 310 ms | |
The resolution of the | 0.1 ms | |
The accuracy of | 3 ms | |
Tripping time limit @ 100% (30 mA) | 300 ms | |
Tripping time limit @ 500% (150 mA) | 40 ms | |
* measured electrical appliances through the mains power supply. |
Environmental indicators | |
Working temperature | 0 to 40 ° C |
Relative humidity | The condensation < 10 ° C |
95%, 10 to 30 ° C | |
75%, 30 to 40 ° C |
Safety indicators | |
Security level | Accordance with the requirements of the third edition EN61010-1 |
CAT II, 300 V, the pollution level 2 |
Machinery and general technical indicators | ||
Size (length x width x height) | 200 x 275 x 114 mm | |
The weight of the | 3.13 kg | |
The power supply | 230 V + 10% to 15%, 50 Hz plus or minus 2 Hz or (only 6500-2:11 0 V + 10% 15%, 50 Hz plus or minus 2 Hz) | |
Power consumption (tester) | 13 W typical (standby) The highest 60 W, 25 a grounding during the test |
|
storage | The temperature | - 10 to 60 ° C |
corrosion | 70 ° C @ 95% Rh, up to five days | |
Work at an altitude of | 0 to 2000 m | |
seal | IP - 40 (shell), IP - 20 (connector) | |
EMC | EN61326-1 standard, portable | |
The perturbation resistance EMI | 3 V/m |
Mode雷竞技appl: Fluke 6500-2 electrical safety tester
- 雷竞技appFluke 6500-2 type portable safety equipment tester
- Quick reference guide
- Hard together with package
- The test line
- The test probe
- Alligator clip
- The power cord
- The USB memory
- The USB cable