雷竞技appFluke 1664 FC multi-function installed tester
The main features
雷竞技appFluke 1664 FC installed tester enables you to comply with all local laws and regulations to test more quickly and efficiently, to may inadvertently connected to the system under test equipment to provide protection, and can easily share test results via smartphones.
- Automatic testing function can test line/loop impedance, RCD tripping current/tripping time, through a single connection and click on the button for insulation test.
- With large current loop mode.And compared in the trip mode RCD circuit test, measurement speed is faster.
- Z - Max storage (circuit test) - easy to evaluate maximum loop test.
- Unique zero adapter to facilitate fast, is reliable and accurate test wire and power compensation.
- Using the power cord fast measurement of L - N, L - voltage between PE and N - PE.Don't need to change the measurement connections.
- Simultaneously measure the RCD tripping current and tripping time (AC type and type A RCD).
- At the same time provide two measurements and double display.At the same time, measure and display the PEFC or PSC and circuit impedance, save time.
- Loop test - use the function button to choose the required input socket - without switching test conductor.
- Automatic startup circuit and RCD test started testing - a supply voltage stability.
- Earth Volt Touchpad can detect more than 50 V grounding voltage rise, indicating potential hazardous situations.
- Attached the safety design of SureGrip ™ test wires and wire clip, to provide users with a comfortable, reliable grip and consistent results.
- Knobs clearly indicating the selected function, all operations together unto one place, and there are no complicated multilevel menu.
- Big screen with a backlight, clear signs and ultra wide Angle of view, to facilitate easy reading safely.
- Pass/fail indication (RCD) test results.
- RCD converter model allows custom Settings.
- Loop resistance and line resistance reach m Ω resolution.
- Sensitive test stable dc RCD (type B).
- Three layer extended memory.
- Using on-off test current measurement of motor winding.
- Affordable 1 meter fall.
- Small and light (less than 1.3 kg) and the accompanying with thick straps, can free hands throughout the test.
Produc雷竞技appts overview: Fluke 1664 FC multi-function installed tester
And a touch protection devices, wireless sharing results, can perform seven tests
雷竞技appFluke 1664 FC installed tester with "insulation pre-test" function.If test instrument to detect device is connected to the system under test, it will stop the insulation test, and help to avoid accidental damage.1664 FC also s雷竞技appupports the use of Fluke Connect®, so, you can send test results to the smartphone, collaborate with other people.Use of automatic testing function, press the button to perform seven test, reduce the number of manual connection and reduce the error probability.
Insulation pre-test
Protection Settings.Avoid costly mistakes.
雷竞技appFluke 1664 FC installed tester is a tester with "insulation pre-test" function, it can be warned of potential errors and avoid causing serious, costly consequences.If test instrument to detect device is connected to the system under test, it will stop the insulation test and provide visual warning.This helps to avoid accidental damage external devices, to reassure users always satisfied.
雷竞技appFluke Connect and FlukeCloud ™ storage
Shared anytime and anywhere.
Even if you and your team is not in the same position also can keep the contact.雷竞技appFluke Connect allows F1664 FC install tester will test results sent to the smart phone, you can contact and collaboration with other people.Information for your team to see what you see, you don't need to leave the scene can be approved.
Retrieve the result of the stored anywhere, anytime
No matter you in t雷竞技apphe office or at the scene, all can through FlukeCloud ™ save storage retrieval results, real-time decision making.In addition, 雷竞技appyou can also use data import Fluke DMS and generate a certificate.Also, you can get the world first-class data protection.Safe, reliable, fast and accurate.Everyt雷竞技apphing comes from Fluke Connect power.
Automatic testing function can shorten test time as high as 40%
Automated testing can be performed in a sequence five necessary installation test, to ensure that the installation of comply with local laws and regulations.It can reduce the manual雷竞技app connection times, reduce the error probability, compared with before the Fluke model, test time can be shortened as much as 40%.
Produc雷竞技appt specifications: Fluke 1664 FC multi-function tester installation
Ac voltage measurement | ||
range | 500 V | |
The resolution of the | 0.1 V | |
The accuracy of 45 Hz and 66 Hz | 0.8% + 3 | |
The input impedance | 360 k Ω | |
Overload protection | True RMS 660 V | |
On-off test (RLO) | ||
Range (switch) | 20 Ω Ω / 200/2000 Ω | |
The resolution of the | 0.01 Ω / 0.1 Ω Ω / 1 | |
The open circuit voltage | > 4 V | |
Measuring insulation resistance (RISO) | ||
The test voltage | 50-100-250-500-1000 V | |
The test voltage precision (under the condition of the test current rating) | + 10% and - 0% | |
The test voltage | 50 V 100 V 250 V 500 V 1000 V |
|
Insulation resistance range | 20 M Ω / 50 M Ω Ω 20 M / 100 M Ω Ω 20 M / 200 M Ω 20 M Ω Ω / 200 M / 500 M Ω 20 M Ω Ω / 200 M / 1000 M Ω |
|
The resolution of the | Ω 0.01 M / 0.1 M Ω Ω 0.01 M / 0.1 M Ω Ω 0.01 M / 0.1 M Ω 0.01 M Ω Ω / 0.1 M / 1 M Ω 0.01 M Ω Ω / 0.1 M / 1 M Ω |
|
Test current | 1 mA @ Ω 50 k 1 mA @ 100 k Ω 1 mA @ 250 k Ω 1 mA @ 500 k Ω 1 mA @ 1 M Ω |
|
The loop impedance and line impedance (ZI) | ||
range | 10 Ω / 0.001 Ω/large current m Ω mode | |
The resolution of the | 0.01 Ω / 0.1 Ω Ω / 1 | |
Potential of ground fault current, the PSC test | ||
range | 1000 A / 10 kA (50 kA) | |
The resolution of the | 1 A / 0.1 kA | |
To calculate | Will supply voltage measurements divided by the loop (L - PE) resistance or lines (L - N) resistance measurements, can calculate the potential of earthing fault current (PEFC) or potential short circuit current (PSC). | |
The types of RCD RCD test, participants | ||
RCD type | AC creates G squared, S after |
|
Model 1664 | A, AC, B= "5", S | |
note | Creates the AC response Squared usually without delay After a delay = "4"The pulse signal response = "5"A smooth dc signal response |
|
Tripping speed tests (Δ T) | ||
Current setting creates | The 10-30-100-10-30-100 mA - VAR The 10-30-100 mA |
|
The multiplier | 1 1/2 level x, x X 5 |
|
Measuring range | G type RCD | 310 ms 50 ms |
S RCD | 510 ms 160 ms |
|
note | Creates 1000 mA (AC) only Maximum 700 mA (under the VAR model, type A) VAR model is not applicable to B. |
|
RCD/FI - tripping current measurement/slope test (I Δ N) | ||
Current range | RCD 30% and 110% of the rated current creates | |
Step length | I Δ 10% of N squared | |
Keep the time | G type | 300 ms/step length |
"S" | 500 ms/step length | |
Accuracy of measurement | Plus or minus 5% | |
The specified tripping current range (EN 61008-1) | From 50% to 100% (AC) From 35% to 140% (type A) (> 10 mA) From 35% to 200% (type A) (mA) 10 or less From 50% to 200% (type B) Squared 5% (type B) |
|
note | Creates A 30% to 150% (type A) I Δ N > 10 mA Between 30% and 210% (type A) I Δ N = 10 mA From 20% to 210% (type B) |
|
Grounding resistance test (RE) | ||
range | 200 Ω / 2000 Ω | |
The resolution of the | 0.1 Ω Ω / 1 | |
frequency | 128 Hz | |
The output voltage | 25 V | |
Phase sequence indicator | ||
icon | Phase sequence indicator is enabled. | |
General technical indicators | ||
Size (length x width x height) | 10 x 25 x 12.5 cm | |
Weight (including battery) | 1.3 Kg | |
The battery specification and quantity | AA type, 6 ea. | |
Seal grade | IP - 40 | |
security | Conform to the EN/IEC 61010-1 and EN/IEC 61010-2-034 | |
overpressure | The CAT III / 500 v, the CAT IV 300 v | |
performance | To EN61557 EN61557-1-7 and EN61557-10 |
Mode雷竞技appl: Fluke 1664 FC multi-function installed tester
雷竞技appFluke 1664 FC multi-function installed tester
The attached:
- 6 AA (IEC) LR6 battery
- C1600 hard portable package
- Zero adapter
- Big load power cord
- STD standard test lead group
- C1600 hard portable package
- With thick straps and belt
- Quick reference guide
- TP165X remote control sensors and wires