雷竞技appFluke1630 earth loop resistance test clamp table
The main features
- Broad grounding resistance measurement range (0.025 Ω Ω 1500), can meet various needs
- 35 mm (1.38 inch) big jaw, can test all kinds of grounding and/or the equipotential bus bar
- Answer the floor drain current measuring range 0.2 mA and 1000 mA, measurement without disconnection, very suitable for system fault diagnosis
- The broad alternating current measuring range (0.2 A to 30 A), suitable for A variety of applications
- User-defined HI/LO alarm limits, can quickly measure evaluation
- Convenient "show hold button for reading on the inaccessible places
- To save time storage function automatic recording and storage of the measured values
- Automatic self calibration, ensure that each measurement is correct
- Overload protection: 200 A
- Enclosed is the portable bag and resistance test loop
- Battery life eight hours or more (work)
Produc雷竞技appts overview: Fluke1630 earth loop resistance test clamp table
Used to measure the commercial, industrial and engineering applications of the grounding resistance
雷竞技appFluke 1630 USES the clamp grounding resistance test technology, greatly simplifies the ground loop testing process, and allow noninvasive leakage current measurement.雷竞技appFluke 1630 compact, durable, very suitable for used in the narrow place and harsh environment, and "show maintain, continuous testing and sound alarm functions make it very easy to use.It USES innovative technology, which means that can be done without a need to cut off the circuit of the ground loop resistance test and continuous testing.
No auxiliary pole test method
雷竞技appFluke 1630 with no auxiliary pole test method, need not disconnect parallel earthing electrode, also need not find suitable place the position of the auxiliary grounding rods.It greatly saves time, and the user (for example, industrial and electrical engineering technicians and on-site maintenance electrician and contractor) can be used in the location of the other technologies (including the tower building internal or wire) ground loop resistance test.No auxiliary pole test method is used, no longer need to earth bar.雷竞技appFluke1630 earth loop resistance test clamp table CARDS around the grounding rods or connection cable.Half of the tester for induction voltage is known, the difference is used to measure current.Tester can automatically determine the grounding connection circuit resistance.
Produc雷竞技appt specifications: Fluke1630 earth loop resistance test clamp table
General technical indicators | |
The operating error | Please refer to working temperature range, guarantee for two years |
Storage temperature range | - 20 ° to 60 ° C (C - 4 ° F to 140 ° F) |
Reference temperature range | 23 ° C + / - 5 ° C (73 ° F + 9 ° F) for |
Store humidity | < 75% RH. |
Working humidity | < 85% RH. |
display | 999 digital LC display, with special symbols |
To protect the | IP30 (according to IEC 529 / EN 60529) |
security | The CAT III 300 V, pollution level 2, IEC 61010-1 and IEC 61010-2-032 |
The weight of the | 750 g (1.165 LBS) |
Wire specifications | About 35 mm (1.38 in) |
Size (length x width x height) | 276 x 100 x 47 mm (10.8 x 3.9 x 1.9 in) |
radiation | IEC 1000-4-2, IEC 61326 - B |
The perturbation resistance | IEC 61000-4-2, 8 kV (air) standard |
IEC 61000-4-3, 3 V/m performance standards | |
Range to choose | automatic |
Overload indicator light | "OL" displayed on the screen |
Measuring time | 0.5 s |
Measure the frequency | 3.333 kHz |
The battery type | 9 V alkaline battery (type IEC 6 LR (61) |
Battery life | For eight hours or more (run) |
Power consumption | 40 mA |
Low battery tips | Display symbols |
Ground loop resistance (automatic range) | |
range | The accuracy of (+ / - % + Ω readings) |
0.025 0.250 Ω | Plus or minus 1.5% plus or minus 0.02 Ω of reading |
0.250 9.999 Ω | Plus or minus 1.5% plus or minus 0.05 Ω of reading |
10.00 99.99 Ω | Plus or minus 2.0% plus or minus 0.3 Ω of reading |
100.0 199.9 Ω | Plus or minus 3.0% plus or minus 1.0 Ω of reading |
200.0 400.0 Ω | Plus or minus 5.0% plus or minus 5 Ω of reading |
400.0 600.0 Ω | Plus or minus 10% plus or minus 10 Ω of reading |
Ω 600.0-1500 | Plus or minus 20% |
No inductance loop resistance, external magnetic field < 50 a/m, the external electric field < 1 V/m, the center conductor. |
Mode雷竞技appl: Fluke1630 earth loop resistance test clamp table
Earth loop resistance test clamp table
Contains:
- Sturdy and straps portable bag
- Resistance test loop
- 9 v battery
- User manual, including English, French, Spanish, German, Italian, Portuguese, and simplified Chinese version