雷竞技appFluke 345 hand-held harmonic power tongs table
The main features
- Ac/dc current:Don't need to cut off the circuit can measure the alternating current (up to 1400 A) and direct current (up to 2000 A)
- Comply with safety standards:CAT IV 600 V power analyzer can be used in the place of inlet
- Accurate measurement in signal-to-noise environment:Armed with low-pass filter, even existed in the electric power load waveform distortion, clamp type table also can be measured accurately
- Data records:For any power quality parameters (including harmonic) for a few minutes or even record more than a month, which found that intermittent failures
- Check the battery:Directly measuring the battery and dc fluctuation of dc system (%)
- Eliminate harmonic problems:Harmonic analysis and records in digital or graph form
- In current:Unpleasant current fluctuation capture and analysis (3 seconds to 300 seconds)
- Simple to use:Used to display the waveform and the trend of wide backlit display, convenient way confirm electric energy measuring instrument Settings
- Three-phase power:Built-in balanced load function
- Check the graphics and generate a report:Record electricity analyzer and the accompanying software
Produc雷竞技appts overview: Fluke 345 hand-held harmonic power tongs table
The clamp type table power quality comprehensive integration of power analyzer, the powerful features of the power quality recorder and clamp type table, is an ideal tool for monitoring power load.
With used to analyze the harmonic spectrum of the highligh雷竞技appt color electric energy meter display, signal-to-noise ratio (SNR) is used to filter out high frequency of the low-pass filter, and excellent electromagnetic anti-interference design, makes the Fluke 345 hand-held harmonic power tongs table is perfect for maintenance of the variable load power quality problems.In addition, with the aid of electric energy meter, hall effect clip-on table can also measure the dc current in the case of without interrupting circuit.Power analyzer's built-in memory allows the user to record the power quality parameter for a long time, so as to analyze trends or intermittent problems.
application
- Set up and maintenance frequency conversion motor, and UPS systems- inspection by measuring the main power quality parameters is working correctly
- Harmonic measurement- found that could damage or destroy the key equipment of the harmonic problems
- Into the current capture- when there is a suspect to reboot or boring trip circuit, check the starting current
- Load analysis- before the increase in load test the capacity of power system
Packing list
Click to download the virtual trialProduc雷竞技appt specifications: Fluke 345 hand-held harmonic power tongs table
Technical specifications | ||
display | Color transmission LCD liquid crystal display, 320 x 240 pixels (diagonal length and 70 mm), secondary backlit | |
The power supply | 1.5 V alkaline battery type AA MN 1500 or IEC LR6 6 x | |
Battery life (typical) | > 10 hours (backlight brightness open) > 12 hours (backlight brightness reduce) |
|
Equivalent battery | The input | 110/230 V 50/60 Hz |
The output | 15 V dc, mA, 300 | |
Environmental conditions (indoor use only) | ||
Reference conditions | All accuracy in 23 ° C + 1 ° C (73.4 ° F + / - 1.8 ° F) under certain | |
Working temperature | 0 ° C to 50 ° C (32 ° F to 122 ° F) | |
Current temperature coefficient | Plus or minus 0.15% or less reading / ° C | |
Voltage temperature coefficient | Plus or minus 0.15% or less reading / ° C | |
Maximum relative humidity | Temperature within 31 ° C (87 ° F) was 80% and the linear reduced to 40 ° C (104 ° F) of 50% | |
Maximum working height | 2000 m | |
Electrical safety | ||
The maximum safe operating voltage | Safety of IEC 61010-1 600 V CAT IV double or reinforced insulation protection, pollution level 2 Protection level IP40;EN60529 |
|
Current measurement | 600 V ac RMS or dc (no insulation between the conductor and ground) | |
Voltage measurement | 600 V ac RMS or dc () between the input terminals and ground or 825 V (plus electric phase voltage) between (triangle network configuration) | |
Electromagnetic compatibility (EMC) | ||
Radiation standards | IEC/EN 61326 - and 97 A | |
The perturbation resistance | IEC/EN 61326 - and 97 B appendix C performance standards | |
mechanical | ||
Size (length x width x height) | 300 x 98 x 52 mm 12 x 3.75 x 2 (in) | |
Weight (including battery) | 820 g (1.8 lb) | |
Jaw opening | 60 mm | |
Jaw capacity | 58 mm diameter | |
clean | You can use the cloth cleaning device is stained with isopropyl alcohol.Do not use abrasives or other solvents. | |
Electrical data | ||
precision | 23 ° C + 1 ° C (73.4 ° F + / - 1.8 ° F).Please see the specifications for temperature coefficient environment conditions. | |
Current measurement (dc, dc RMS, ac RMS) | ||
Measuring range | 0-2000 - A dc or ac 1400 valid values | |
Automatic range | 40 A / 400 A / 2000 A | |
The resolution of the | A range of 40 for 10 mA 400 A range of 100 mA A, in 2000 A range |
|
Accuracy: dc and dc valid values | I > 10 A | Plus or minus five plus or minus 1.5% |
I < 10 A | Plus or minus 0.2 A | |
The average accuracy: | I > 10 A | Reading plus or minus 3% plus or minus five words |
I < 10 A | Plus or minus 0.5 A | |
Accuracy: peak | I > 10 A | Plus or minus five plus or minus 5% |
I < 10 A | Plus or minus 0.5 A | |
Accuracy: AHr | I > 10 A | Plus or minus five plus or minus 2% |
I < 10 A | + / - 0.5 AHr | |
Accuracy: CF (crest factor) | 1.1 the CF or less < 3 | Plus or minus five plus or minus 3% |
3 the CF or less < 5 | Plus or minus five plus or minus 5% | |
The resolution of the | 0.01 | |
Accuracy: RPL (ripple) | 2% or less RPL < 100% | Plus or minus five plus or minus 3% |
100% or less RPL < 600% | Plus or minus five plus or minus 5% | |
The resolution of the | 0.1% | |
I dc > 5 A, I > 2 A communication | ||
All measurements are in direct current (DC) and 15 Hz to 1 kHz conditions Maximum overload 10000 A or RMS x frequency < 400000 Ampere valid values for true RMS measurement (ac + dc) |
||
Voltage measurement (dc, dc RMS, ac RMS) | ||
Measuring range | 0 to 825 V dc or ac RMS | |
Automatic range | 4 40 V/V / 400 V / 750 V | |
The resolution of the | 4 V range for 1 mV Under 40 V range for 10 mV 400 V range is 100 mV 750 V range of 1 V |
|
Accuracy: dc and dc valid values | V > 1 V | Plus or minus five plus or minus 1% |
V < 1 V | + / - 0.02 V | |
The average accuracy: | V > 1 V | Plus or minus five plus or minus 3% |
V < 1 V | + / - 0.03 V | |
Accuracy: peak | V > 1 V | Plus or minus five plus or minus 5% |
V < 1 V | + / - 0.03 V | |
Accuracy: CF (crest factor) | 1.1 the CF or less < 3 | Plus or minus five plus or minus 3% |
3 the CF or less < 5 | Plus or minus five plus or minus 5% | |
The resolution of the | 0.01 | |
Accuracy: RPL (ripple) | 2% or less RPL < 100% | Plus or minus five plus or minus 3% |
100% or less RPL < 600% | Plus or minus five plus or minus 5% | |
The resolution of the | 0.1% | |
V dc > 0.5 V, V ac > 0.2 V | ||
All measurements are in direct current (DC) and 15 Hz to 1 kHz conditions Maximum overload 1000 V RMS Voltage RMS for true RMS measurement (ac + dc) |
||
harmonic | ||
THD (total harmonic distortion) | 1% or less THD < 100% | Plus or minus five plus or minus 3% |
100% or less THD < 600% | Plus or minus five plus or minus 5% | |
The resolution of the | 0.1% | |
DF (distortion coefficient) | 1% or less DF < 100% | Plus or minus five plus or minus 3% |
The resolution of the | 0.1% | |
H02 Vharm or less < H13 | Plus or minus 5% plus or minus two | |
H13 Vharm H30 or less or less | Plus or minus 10% plus or minus two | |
All measured up to 30 times harmonic (15 Hz to 22 Hz for up to 40 times harmonic) The fundamental wave F0The frequency range of 45 Hz to 15 Hz to 22 Hz and 65 Hz Vacrms > 1 v |
||
Power measurement (single-phase and three-phase) (dc, dc RMS, ac RMS) | ||
Measuring range | 0 to 1650 kW dc or 1200 kW ac | |
Measuring range | 4 kW and 40 kW to 400 kW, 1650 kW | |
The resolution of the | 4 kW for 1 W Under 40 kW of 10 W 400 kW to 100 W Under the 1200 kW to 1 kW |
|
precision | The 2.5% reading plus or minus five W1 Ø < 2 kW + / - 0.08 kW The W3 Ø < 4 kW + / - 0.25 kW |
|
VA measurement (single-phase and three-phase) (dc, dc RMS, ac RMS) | ||
Measuring range | 0 to dc or ac 1200 kVA, 1650 kVA | |
Automatic range | 4 kVA, 40 kVA, 400 kVA, 1650 kVA | |
The resolution of the | 1 VA under 4 kVA For 10 VA under 40 kVA Under the 400 kVA is 100 VA Under the 1200 kVA is 1 kVA |
|
precision | VA > 2 kVA | The 2.5% reading plus or minus five |
VA < 2 kVA | + / - 0.08 kVA | |
VAR measurement (single-phase and three-phase) | ||
Measuring range | 0 to 1250 kVAR | |
Automatic range | 4 kVAR, 40 kVAR, 400 kVAR, 1200 kVAR | |
The resolution of the | 4 to 1 under kVAR VAR Under 40 kVAR for 10 VAR 400 kVAR 100 VAR 1200 kVAR 1 kVAR |
|
precision | VAR > 4 kVAR | Plus or minus five plus or minus 2.5% |
VAR < 4 kVAR | + / - 0.25 kVAR | |
Scope of the power factor | 0.3 < PF < 0.99 | |
The power factor (single-phase and three-phase) | ||
Measuring range | 0.3 inductance capacitance to 1.0 and 1.0 to 0.3 (between 0 ° and 72.5 ° capacitance 0 ° and 72.5 ° inductance) | |
The resolution of the | 0.001 | |
precision | Plus or minus 3 ° | |
Frequency range | 15 Hz to 1 kHz | |
The displacement power factor (single-phase and three-phase) | ||
Measuring range | 0.3 inductance capacitance to 1.0 and 1.0 to 0.3 (between 0 ° and 72.5 ° capacitance 0 ° and 72.5 ° inductance) | |
The resolution of the | 0.001 | |
precision | Plus or minus 3 ° | |
Frequency range | 45 Hz to 15 Hz to 22 Hz and 65 Hz | |
KWH (kWHr) | ||
Measuring range | 40000 kWHr | |
Automatic range | 4 kWHr, 40 kWHr, 400 kWHr, 4000 kWHr, 40000 kWHr | |
The resolution of the | 4 kWHr range for 1 WHr Under 40 kWHr range for 10 WHr 400 kWHr range for 100 WHr KWHr kWHr 4000 range for 1 40000 kWHr range for 10 kWHr |
|
precision | KWHr kWHr > 2 | Plus or minus 3% plus or minus five |
KWHr kWHr < 2 | + / - 0.08 kWHr | |
All of the active power (Watts)/apparent power (VA)/reactive power (VAR)/power factor (PF) measurements | Frequency range | Dc and 15 Hz to 1 kHz |
Current range | 10 A to 1400 A valid value | |
Voltage range | 1 V to 825 V RMS | |
Maximum input | 3 825 V / 1400 A valid value | |
Maximum overload | 3 1000 V / 10000 A all measurement under the condition of dc and 15 Hz to 1 kHz to maximum overload 10000 A or valid frequency x < 400000 | |
Frequency measurement (from a current or voltage source) | ||
Measuring range | 15 Hz to 1 kHz | |
The resolution of the | 0.1 Hz | |
precision | 15 and 22 Hz plus or minus 0.5% reading 40 Hz - 70 Hz plus or minus 0.5% reading 15 Hz - 1000 Hz plus or minus 1% reading |
|
Current range | 10 A to 1400 A valid value | |
Voltage range | 1 V to 825 V RMS | |
Oscilloscope function | ||
Current measurement | range | 10 A/A / 40, 20 A / 100 A / 200 A / 400 A / 1000 A / 2000 A |
The resolution of the | A 40 to 1 A 400 A for 10 A 2000 A under 50 A |
|
precision | The plus or minus 3% reading plus or minus 1 pixel | |
Maximum overload | 10000 A | |
Voltage measurement | range | 4 V / 10 V/V / 20 to 40 V / 100 V / 200 V / 400 V / 1000 V |
The resolution of the | 4 V for 100 mV Under 40 V for 1 V Under the 400 V to 10 V Under the 1000 V to 31.25 V |
|
precision | The plus or minus 2% reading plus or minus 1 pixel | |
Maximum overload | True RMS 1000 V | |
Frequency range | Dc and 15 Hz - 600 Hz | |
Time base | 2.5 ms, 5 ms, 10 ms, 25 ms, 50 ms/div (ms) | |
The refresh rate | 0.5 seconds | |
Maximum sampling rate | 15.625 kHz | |
The surge current function | ||
range | A 40, 400 A and 2000 A | |
The resolution of the | A range of 40 for 10 mA 400 A range of 100 mA 2000 A range of 1 A |
|
precision | I > 10 A | The plus or minus 5% reading plus or minus 1 pixel |
I < 10 A | Plus or minus 0.5 A | |
All measurements are in direct current (DC) and 15 Hz to 1 kHz conditions | ||
Maximum overload | Maximum overload 10000 A or RMS x frequency < 400000 Ampere valid values for true RMS measurement (ac + dc) |
|
Capture time | 1 s, 3 s, 10 s, 30 s, 100 s and 300 s | |
Maximum sampling rate | 15.625 kHz | |
interface | ||
USB PC interface | Power the Log (electricity) software is used to download, analysis and reporting 345 Upgrade Utility Utility (Upgrade) is used to install the new firmware version |
|
Record the memory | ||
Record the area | There are three areas, can be used alone, or one of a large area | |
Average period | 1 second, 2 seconds, 5 seconds, 10 seconds, 30 seconds and 1 minute, 5 points, 10 points, 15 points and custom | |
Recording time | ||
Voltage and current mode | The average time | Record time (1) |
1 second | 1 49 points | |
2 seconds, | 3 when 38 points | |
5 seconds | 9 when 6 points | |
10 seconds | 18 when 12 points | |
30 seconds | 2, 6 36 points | |
1 min (mv) | 4, 13, 12 points | |
5 min (mv) | 22 when 18 0 | |
Ten minutes | 12 when 45 day 0 | |
15 min (mv) | 68 days, 6 0 | |
Record time (3) | ||
1 second | 5 12 points | |
2 seconds, | 10 when 24 points | |
5 seconds | 00 points 1, 2 | |
10 seconds | 00 2, 4 points | |
30 seconds | 1 minute, 6, 12 | |
1 min (mv) | 13, 0 12 points | |
5 min (mv) | 65 - day 0 15 points | |
Ten minutes | 130 - day 0 when 30 points | |
15 min (mv) | When the 195 - day 0 45 points | |
The V and A harmonic model | The average time | Record time (1) |
1 second | 0 34 points | |
2 seconds, | 1 eight points | |
5 seconds | 2 when the 52 points | |
10 seconds | 44 points by 5 | |
30 seconds | 17 when 13 points | |
1 meter | 1, 10 with 26 points | |
5 m. | 7, 4 when 10 points | |
10 m. | 14 when the 8 20 points | |
15 m. | 21, 12 when 30 points | |
Record time (3) | ||
1 second | 1 38 points | |
2 seconds, | 3 when 16 points | |
5 seconds | At 11 points | |
10 seconds | 16 23 points | |
30 seconds | 2, 1 11 points | |
1 meter | 4, 2 with 23 points | |
5 m. | When 20 November 25 points | |
10 m. | 81 - day 0 50 points | |
15 m. | When the 121 - day 13 to 15 points | |
Single-phase and three-phase power mode | The average time | Record time (1) |
1 second | 1 when 40 points | |
2 seconds, | 3 when 21 points | |
5 seconds | At 8 22 points | |
10 seconds | At 16 | |
30 seconds | 2, 2 to 17 points | |
1 meter | 4, 4 when 35 points | |
5 m. | 55 points 20 to 22 | |
10 m. | 41 days 21 50 points | |
15 m. | 62 days at 20 | |
Record time (3) | ||
1 second | 4 when 47 points | |
2 seconds, | At 34 points | |
5 seconds | 23 when 57 points | |
10 seconds | 1, 54 points by 23 | |
30 seconds | 5, 23 25 points | |
1 meter | 11, 23 25 points | |
5 m. | 59 days 21 when five points | |
10 m. | 119 18 10 points | |
15 m. | 15 points and 15 179 days |
Mode雷竞技appl: Fluke 345 hand-held harmonic power tongs table
Power quality clamp type table
Contains:
- 345 power quality clamp type table
- Soft portable package
- Electricity record software
- The test line
- Alligator clip
- The test probe
- The USB cable
- International communication adapter/transfer boxes
- English user manual printing
- Multilingual manual CD