雷竞技appFluke 345 hand-held harmonic power tongs table

  • 雷竞技appFluke 345 Power Quality Clamp Meter
Has been discontinued

The main features

  • Ac/dc current:Don't need to cut off the circuit can measure the alternating current (up to 1400 A) and direct current (up to 2000 A)
  • Comply with safety standards:CAT IV 600 V power analyzer can be used in the place of inlet
  • Accurate measurement in signal-to-noise environment:Armed with low-pass filter, even existed in the electric power load waveform distortion, clamp type table also can be measured accurately
  • Data records:For any power quality parameters (including harmonic) for a few minutes or even record more than a month, which found that intermittent failures
  • Check the battery:Directly measuring the battery and dc fluctuation of dc system (%)
  • Eliminate harmonic problems:Harmonic analysis and records in digital or graph form
  • In current:Unpleasant current fluctuation capture and analysis (3 seconds to 300 seconds)
  • Simple to use:Used to display the waveform and the trend of wide backlit display, convenient way confirm electric energy measuring instrument Settings
  • Three-phase power:Built-in balanced load function
  • Check the graphics and generate a report:Record electricity analyzer and the accompanying software

This product has been discontinued or reclassified

Produc雷竞技appts overview: Fluke 345 hand-held harmonic power tongs table

Suggestions to the fluke official flagship store of purchase

The clamp type table power quality comprehensive integration of power analyzer, the powerful features of the power quality recorder and clamp type table, is an ideal tool for monitoring power load.

With used to analyze the harmonic spectrum of the highligh雷竞技appt color electric energy meter display, signal-to-noise ratio (SNR) is used to filter out high frequency of the low-pass filter, and excellent electromagnetic anti-interference design, makes the Fluke 345 hand-held harmonic power tongs table is perfect for maintenance of the variable load power quality problems.In addition, with the aid of electric energy meter, hall effect clip-on table can also measure the dc current in the case of without interrupting circuit.Power analyzer's built-in memory allows the user to record the power quality parameter for a long time, so as to analyze trends or intermittent problems.

application

  • Set up and maintenance frequency conversion motor, and UPS systems- inspection by measuring the main power quality parameters is working correctly
  • Harmonic measurement- found that could damage or destroy the key equipment of the harmonic problems
  • Into the current capture- when there is a suspect to reboot or boring trip circuit, check the starting current
  • Load analysis- before the increase in load test the capacity of power system

Produc雷竞技appt specifications: Fluke 345 hand-held harmonic power tongs table

Technical specifications
display Color transmission LCD liquid crystal display, 320 x 240 pixels (diagonal length and 70 mm), secondary backlit
The power supply 1.5 V alkaline battery type AA MN 1500 or IEC LR6 6 x
Battery life (typical) > 10 hours (backlight brightness open)
> 12 hours (backlight brightness reduce)
Equivalent battery The input 110/230 V 50/60 Hz
The output 15 V dc, mA, 300
Environmental conditions (indoor use only)
Reference conditions All accuracy in 23 ° C + 1 ° C (73.4 ° F + / - 1.8 ° F) under certain
Working temperature 0 ° C to 50 ° C (32 ° F to 122 ° F)
Current temperature coefficient Plus or minus 0.15% or less reading / ° C
Voltage temperature coefficient Plus or minus 0.15% or less reading / ° C
Maximum relative humidity Temperature within 31 ° C (87 ° F) was 80% and the linear reduced to 40 ° C (104 ° F) of 50%
Maximum working height 2000 m
Electrical safety
The maximum safe operating voltage Safety of IEC 61010-1 600 V CAT IV double or reinforced insulation protection, pollution level 2
Protection level IP40;EN60529
Current measurement 600 V ac RMS or dc (no insulation between the conductor and ground)
Voltage measurement 600 V ac RMS or dc () between the input terminals and ground or 825 V (plus electric phase voltage) between (triangle network configuration)
Electromagnetic compatibility (EMC)
Radiation standards IEC/EN 61326 - and 97 A
The perturbation resistance IEC/EN 61326 - and 97 B appendix C performance standards
mechanical
Size (length x width x height) 300 x 98 x 52 mm 12 x 3.75 x 2 (in)
Weight (including battery) 820 g (1.8 lb)
Jaw opening 60 mm
Jaw capacity 58 mm diameter
clean You can use the cloth cleaning device is stained with isopropyl alcohol.Do not use abrasives or other solvents.
Electrical data
precision 23 ° C + 1 ° C (73.4 ° F + / - 1.8 ° F).Please see the specifications for temperature coefficient environment conditions.
Current measurement (dc, dc RMS, ac RMS)
Measuring range 0-2000 - A dc or ac 1400 valid values
Automatic range 40 A / 400 A / 2000 A
The resolution of the A range of 40 for 10 mA
400 A range of 100 mA
A, in 2000 A range
Accuracy: dc and dc valid values I > 10 A Plus or minus five plus or minus 1.5%
I < 10 A Plus or minus 0.2 A
The average accuracy: I > 10 A Reading plus or minus 3% plus or minus five words
I < 10 A Plus or minus 0.5 A
Accuracy: peak I > 10 A Plus or minus five plus or minus 5%
I < 10 A Plus or minus 0.5 A
Accuracy: AHr I > 10 A Plus or minus five plus or minus 2%
I < 10 A + / - 0.5 AHr
Accuracy: CF (crest factor) 1.1 the CF or less < 3 Plus or minus five plus or minus 3%
3 the CF or less < 5 Plus or minus five plus or minus 5%
The resolution of the 0.01
Accuracy: RPL (ripple) 2% or less RPL < 100% Plus or minus five plus or minus 3%
100% or less RPL < 600% Plus or minus five plus or minus 5%
The resolution of the 0.1%
I dc > 5 A, I > 2 A communication
All measurements are in direct current (DC) and 15 Hz to 1 kHz conditions
Maximum overload 10000 A or RMS x frequency < 400000
Ampere valid values for true RMS measurement (ac + dc)
Voltage measurement (dc, dc RMS, ac RMS)
Measuring range 0 to 825 V dc or ac RMS
Automatic range 4 40 V/V / 400 V / 750 V
The resolution of the 4 V range for 1 mV
Under 40 V range for 10 mV
400 V range is 100 mV
750 V range of 1 V
Accuracy: dc and dc valid values V > 1 V Plus or minus five plus or minus 1%
V < 1 V + / - 0.02 V
The average accuracy: V > 1 V Plus or minus five plus or minus 3%
V < 1 V + / - 0.03 V
Accuracy: peak V > 1 V Plus or minus five plus or minus 5%
V < 1 V + / - 0.03 V
Accuracy: CF (crest factor) 1.1 the CF or less < 3 Plus or minus five plus or minus 3%
3 the CF or less < 5 Plus or minus five plus or minus 5%
The resolution of the 0.01
Accuracy: RPL (ripple) 2% or less RPL < 100% Plus or minus five plus or minus 3%
100% or less RPL < 600% Plus or minus five plus or minus 5%
The resolution of the 0.1%
V dc > 0.5 V, V ac > 0.2 V
All measurements are in direct current (DC) and 15 Hz to 1 kHz conditions
Maximum overload 1000 V RMS
Voltage RMS for true RMS measurement (ac + dc)
harmonic
THD (total harmonic distortion) 1% or less THD < 100% Plus or minus five plus or minus 3%
100% or less THD < 600% Plus or minus five plus or minus 5%
The resolution of the 0.1%
DF (distortion coefficient) 1% or less DF < 100% Plus or minus five plus or minus 3%
The resolution of the 0.1%
H02 Vharm or less < H13 Plus or minus 5% plus or minus two
H13 Vharm H30 or less or less Plus or minus 10% plus or minus two
All measured up to 30 times harmonic (15 Hz to 22 Hz for up to 40 times harmonic)
The fundamental wave F0The frequency range of 45 Hz to 15 Hz to 22 Hz and 65 Hz
Vacrms > 1 v
Power measurement (single-phase and three-phase) (dc, dc RMS, ac RMS)
Measuring range 0 to 1650 kW dc or 1200 kW ac
Measuring range 4 kW and 40 kW to 400 kW, 1650 kW
The resolution of the 4 kW for 1 W
Under 40 kW of 10 W
400 kW to 100 W
Under the 1200 kW to 1 kW
precision The 2.5% reading plus or minus five
W1 Ø < 2 kW + / - 0.08 kW
The W3 Ø < 4 kW + / - 0.25 kW
VA measurement (single-phase and three-phase) (dc, dc RMS, ac RMS)
Measuring range 0 to dc or ac 1200 kVA, 1650 kVA
Automatic range 4 kVA, 40 kVA, 400 kVA, 1650 kVA
The resolution of the 1 VA under 4 kVA
For 10 VA under 40 kVA
Under the 400 kVA is 100 VA
Under the 1200 kVA is 1 kVA
precision VA > 2 kVA The 2.5% reading plus or minus five
VA < 2 kVA + / - 0.08 kVA
VAR measurement (single-phase and three-phase)
Measuring range 0 to 1250 kVAR
Automatic range 4 kVAR, 40 kVAR, 400 kVAR, 1200 kVAR
The resolution of the 4 to 1 under kVAR VAR
Under 40 kVAR for 10 VAR
400 kVAR 100 VAR
1200 kVAR 1 kVAR
precision VAR > 4 kVAR Plus or minus five plus or minus 2.5%
VAR < 4 kVAR + / - 0.25 kVAR
Scope of the power factor 0.3 < PF < 0.99
The power factor (single-phase and three-phase)
Measuring range 0.3 inductance capacitance to 1.0 and 1.0 to 0.3 (between 0 ° and 72.5 ° capacitance 0 ° and 72.5 ° inductance)
The resolution of the 0.001
precision Plus or minus 3 °
Frequency range 15 Hz to 1 kHz
The displacement power factor (single-phase and three-phase)
Measuring range 0.3 inductance capacitance to 1.0 and 1.0 to 0.3 (between 0 ° and 72.5 ° capacitance 0 ° and 72.5 ° inductance)
The resolution of the 0.001
precision Plus or minus 3 °
Frequency range 45 Hz to 15 Hz to 22 Hz and 65 Hz
KWH (kWHr)
Measuring range 40000 kWHr
Automatic range 4 kWHr, 40 kWHr, 400 kWHr, 4000 kWHr, 40000 kWHr
The resolution of the 4 kWHr range for 1 WHr
Under 40 kWHr range for 10 WHr
400 kWHr range for 100 WHr
KWHr kWHr 4000 range for 1
40000 kWHr range for 10 kWHr
precision KWHr kWHr > 2 Plus or minus 3% plus or minus five
KWHr kWHr < 2 + / - 0.08 kWHr
All of the active power (Watts)/apparent power (VA)/reactive power (VAR)/power factor (PF) measurements Frequency range Dc and 15 Hz to 1 kHz
Current range 10 A to 1400 A valid value
Voltage range 1 V to 825 V RMS
Maximum input 3 825 V / 1400 A valid value
Maximum overload 3 1000 V / 10000 A all measurement under the condition of dc and 15 Hz to 1 kHz to maximum overload 10000 A or valid frequency x < 400000
Frequency measurement (from a current or voltage source)
Measuring range 15 Hz to 1 kHz
The resolution of the 0.1 Hz
precision 15 and 22 Hz plus or minus 0.5% reading
40 Hz - 70 Hz plus or minus 0.5% reading
15 Hz - 1000 Hz plus or minus 1% reading
Current range 10 A to 1400 A valid value
Voltage range 1 V to 825 V RMS
Oscilloscope function
Current measurement range 10 A/A / 40, 20 A / 100 A / 200 A / 400 A / 1000 A / 2000 A
The resolution of the A 40 to 1 A
400 A for 10 A
2000 A under 50 A
precision The plus or minus 3% reading plus or minus 1 pixel
Maximum overload 10000 A
Voltage measurement range 4 V / 10 V/V / 20 to 40 V / 100 V / 200 V / 400 V / 1000 V
The resolution of the 4 V for 100 mV
Under 40 V for 1 V
Under the 400 V to 10 V
Under the 1000 V to 31.25 V
precision The plus or minus 2% reading plus or minus 1 pixel
Maximum overload True RMS 1000 V
Frequency range Dc and 15 Hz - 600 Hz
Time base 2.5 ms, 5 ms, 10 ms, 25 ms, 50 ms/div (ms)
The refresh rate 0.5 seconds
Maximum sampling rate 15.625 kHz
The surge current function
range A 40, 400 A and 2000 A
The resolution of the A range of 40 for 10 mA
400 A range of 100 mA
2000 A range of 1 A
precision I > 10 A The plus or minus 5% reading plus or minus 1 pixel
I < 10 A Plus or minus 0.5 A
All measurements are in direct current (DC) and 15 Hz to 1 kHz conditions
Maximum overload Maximum overload 10000 A or RMS x frequency < 400000
Ampere valid values for true RMS measurement (ac + dc)
Capture time 1 s, 3 s, 10 s, 30 s, 100 s and 300 s
Maximum sampling rate 15.625 kHz
interface
USB PC interface Power the Log (electricity) software is used to download, analysis and reporting
345 Upgrade Utility Utility (Upgrade) is used to install the new firmware version
Record the memory
Record the area There are three areas, can be used alone, or one of a large area
Average period 1 second, 2 seconds, 5 seconds, 10 seconds, 30 seconds and 1 minute, 5 points, 10 points, 15 points and custom
Recording time
Voltage and current mode The average time Record time (1)
1 second 1 49 points
2 seconds, 3 when 38 points
5 seconds 9 when 6 points
10 seconds 18 when 12 points
30 seconds 2, 6 36 points
1 min (mv) 4, 13, 12 points
5 min (mv) 22 when 18 0
Ten minutes 12 when 45 day 0
15 min (mv) 68 days, 6 0
Record time (3)
1 second 5 12 points
2 seconds, 10 when 24 points
5 seconds 00 points 1, 2
10 seconds 00 2, 4 points
30 seconds 1 minute, 6, 12
1 min (mv) 13, 0 12 points
5 min (mv) 65 - day 0 15 points
Ten minutes 130 - day 0 when 30 points
15 min (mv) When the 195 - day 0 45 points
The V and A harmonic model The average time Record time (1)
1 second 0 34 points
2 seconds, 1 eight points
5 seconds 2 when the 52 points
10 seconds 44 points by 5
30 seconds 17 when 13 points
1 meter 1, 10 with 26 points
5 m. 7, 4 when 10 points
10 m. 14 when the 8 20 points
15 m. 21, 12 when 30 points
Record time (3)
1 second 1 38 points
2 seconds, 3 when 16 points
5 seconds At 11 points
10 seconds 16 23 points
30 seconds 2, 1 11 points
1 meter 4, 2 with 23 points
5 m. When 20 November 25 points
10 m. 81 - day 0 50 points
15 m. When the 121 - day 13 to 15 points
Single-phase and three-phase power mode The average time Record time (1)
1 second 1 when 40 points
2 seconds, 3 when 21 points
5 seconds At 8 22 points
10 seconds At 16
30 seconds 2, 2 to 17 points
1 meter 4, 4 when 35 points
5 m. 55 points 20 to 22
10 m. 41 days 21 50 points
15 m. 62 days at 20
Record time (3)
1 second 4 when 47 points
2 seconds, At 34 points
5 seconds 23 when 57 points
10 seconds 1, 54 points by 23
30 seconds 5, 23 25 points
1 meter 11, 23 25 points
5 m. 59 days 21 when five points
10 m. 119 18 10 points
15 m. 15 points and 15 179 days

Mode雷竞技appl: Fluke 345 hand-held harmonic power tongs table

雷竞技appFluke 345

Power quality clamp type table

Contains:

  • 345 power quality clamp type table
  • Soft portable package
  • Electricity record software
  • The test line
  • Alligator clip
  • The test probe
  • The USB cable
  • International communication adapter/transfer boxes
  • English user manual printing
  • Multilingual manual CD