The main features

  • Insulation testing range:
    • Ω 0.1 M to 2000 M Ω
  • Insulation test voltage:
    • 500 V, 1000 V
  • Remote testing probe is easy to repeat the test and test execution in inaccessible places
  • Real-time circuit detection function is prohibited in the test the insulation voltage higher than 30 V, and raise the level of security
  • Automatic release of capacitive voltage can better protect the safety of the user
  • Ac/dc voltage: 0.1 V to 600 V
  • Continuous current 200 mA
  • Ω Ω resistance: 0.01 to 20.00 k
  • Automatic shutdown function to save the battery
  • Wide backlit display measurement results easy to read
  • CAT 600 V overvoltage category IV level with the user's security level
  • Each tester with remote probe, test line, probe and alligator clip
  • Equipp雷竞技apped with optional Fluke TPAK magnetic suspension system enables you to to work in the other
  • 4 AA alkaline batteries (NEDA 15 A or IEC LR6) can be at least 1000 times the insulation test
  • One year warranty

Produc雷竞技appts overview: Fluke 1503 insulation resistance tester

雷竞技appFluke 1503 insulation tester is exquisitely meticulous, sturdy, and the operation is very convenient.Because can accept a variety of test voltage, they become ideal tool maintenance, debugging, and preventive maintenance.

These tools also equipped with a remote probe and other components, which makes the testing process is very fast, and saves cost.

More has the following official authorization Tmall stores, for you to choose a suitable way to purchase:
雷竞技appFluke music store 雷竞技appFluke west light stores 雷竞技appFluke Fluke benevolence, stores
雷竞技appFluke founded new jie stores 雷竞技appFluke ruitai cable stores 雷竞技appFluke ray stores
雷竞技appA Fluke kechuang store


Insulation resistance meter the normal operation of the demonstration

Handheld bridge (resistance/capacitance/inductance tester) fluke ember LCR55A

Produc雷竞技appt specifications: Fluke 1503 insulation resistance tester

Ac/dc voltage measurement
precision range 600.0 V
The resolution of the 0.1 V
50 Hz - 400 Hz + (reading % + digits) Plus or minus 2% (+ 3)
The input impedance 3 M Ω (nominal), < 100 pF
Attenuation common-mode (1 k Ω imbalance) When the dc > 60 dB, 50 or 60 Hz
Overload protection The RMS or dc 600 V
Ground connection resistance measurements
The scope/resolution 20.00 Ω 0.01 Ω
200.0 Ω 0.1 Ω
2000 Ω 1.0 Ω
20.00 k Ω 0.01 k Ω
precision Plus or minus 1.5% (+ 3)
Overload protection 2 V RMS or dc
Open circuit voltage > 4.0 V, < 8 V
Short circuit current > 200.0 mA
The insulation specification
Measured value range Ω 0.01 M to 2000 M Ω
The test voltage 500 V, 1000 V
The test voltage accuracy + 20% and - 0%
Short circuit current 1 mA (nominal)
Automatic discharge Discharge time < 0.5 seconds, C = 1 (including F or less
Electric circuit indicator Before the initial test, if the terminal voltage > 30 V, inhibition test
The biggest capacitive loads Under 1 (including F load operation
Accuracy of measurement
The output voltage Display range The resolution of the Test current precision
+ + (% readings for the lowest effective quantity)
500 V (0% to + 20%)
0.1 to 20.0 M Ω 0.01 M Ω 1 mA @
500 k Ω
Plus or minus 2.0% (+ 5)
20.0 to 200.0 M Ω 0.1 M Ω
Between 200 and 500 M Ω 1 M Ω
1000 V (0% to + 20%) 0.1 to 200.0 M Ω 0.1 M Ω 1 mA @
1 M Ω
Plus or minus 2.0% (+ 5)
Between 200 and 2000 M Ω 1 M Ω
General technical indicators
Applying to any of the maximum voltage terminal: 600 V AC RMS or DC
Storage temperature - 40 ° to 60 ° C - C (to 40 ° F to 140 ° F)
Working temperature - 20 ° C to 55 ° C (4 ° F to 131 ° F)
The temperature coefficient of 28 ° C temperature 18 ° C < or > (< > 64 ° F or 82 ° F), 0.05 x (specified accuracy) / ° C
Relative humidity
10 ° to 30 ° C C (50 ° F to 86 ° F), 0% to 95%
30 ° C to 40 ° C (86 ° F to 104 ° F), 0% to 75%
40 ° C to 55 ° C (104 ° F to 131 ° F), 0% to 40%
vibration Random, 2 g, 5-500 Hz, based on MIL - PRF - 28800 - f 2 kind of instruments
The impact In accordance with the provisions of IEC 61010-1 version 2, 1 m drop (1 m drop test, six sides, oak floor)
Electromagnetic compatibility In a 3 V/M radio frequency magnetic field, precision = specified precision (EN 61326-97) took
security Meet the ANSI/ISA 82.02.01 (2004, 61010-1) CAN/CSA - C22.2 NO. 61010-1-04, and IEC/EN 61010-1 version 2, class IV measuring 600 V (IV)
certification CSA according to the standard CSA/CAN C22.2 No. 61010.1-04;TUV according to the standard of IEC/EN 61010-1 version 2
The battery 4 AA batteries (NEDA 15 a or IEC LR6)
Battery life Insulation testing purposes: Room temperature, the new alkaline batteries for instrument for at least 1000 times the insulation test.The results of the standard is in 1000 V through 1 M Ω resistance measured, under the condition of the cycle time for 5 seconds, 25 seconds.
Resistance measurement: Room temperature, the new alkaline batteries for insulation measurement instrument for at least 2500 times earth connection.The results of the standard is in the case of 1 Ω resistance measured, the cycle time for 5 seconds, 25 seconds.
Size (height x width x length) 5.0 x 10.0 x 20.3 cm (1.97 x 3.94 x 8.00 in)
The weight of the 550 g (1.2 lb)
IP protection grade IP40
At an altitude of Work at an altitude of 2000 m CAT IV 600 V, 3000 m CAT III 600 V
Not operation (deposit) 12000 m
Excess capacity 110% range
It contains the attachment TL224 test conductor, TP74 test probes, clip part number is 1958654 (red) and 1958646 (black), holster and remote probe

Mode雷竞技appl: Fluke 1503 insulation resistance tester

雷竞技appFLUKE - 1503.

Insulation multimeter

Include:

  • Remote probe
  • The test lead
  • The test probe
  • Spring clip
  • holster
  • The user manual