雷竞技appThree-phase power quality recorder instrument Fluke 1736 and 1738
The main features
雷竞技appFluke, 1736 and 1738, three-phase power quality recorder is a multipurpose, compatible with Fluke Connect three-phase power recorder, used to perform energy, load and power quality research
- The main measures:Automatically capture and record the voltage, current, power, harmonic and the associated power quality, value, and use the incident wave snapshots and high resolution true RMS configuration file capture sag, transient and surge current
- Convenient instrument power supply:Directly from the measuring instrument circuit for power supply
- Energy Analyze Plus application software:Through our automated reporting functions download and analyze the energy consumption and power quality of the health of every detail, and using the integrated power quality health to quickly understand the health status of the system
Produc雷竞技appts overview: Fluke three-phase power quality recorder instrument for 1736 and 1738
雷竞技appThree-phase power quality recorder has a Fluke Fluke 1736 and 1738 the Connect ® mobile applications and desktop software compatibility, allowing you to obtain the required data, thus making real-time power quality and energy consumption decisions.1736 and 1738 to electric energy analysis and basic power quality records, is the ideal testing tools, automatically acquire and record more than 500 power quality parameters, let you have a better visibility on the required data, in order to optimize system reliability and save money.Wit雷竞技apph the help of a Fluke 1738 advanced power quality recorder, you can use to enhance the power quality health profile "(EN50160) function to perform advanced analysis, allows you to quickly understand the electrical system's overall health.Power quality health profile is based on the detailed power quality measurement for the evaluation of the data recorded, including visual event waveform capture, allowing you to have better visibility, the data needed to optimize the system reliability and save electricity.
Through optimization of the user interface, flexible current probe and function of intelligent measurement verification, you can through the verification and correction of common connection error to reduce the measurement error, makes the setting more convenient than ever before, reduce the measurement uncertainty.By 雷竞技appFluke Connect ® application remote access to data and share them with your team, let you can keep more safe working distance and real-time to make important decisions, reduce the use of protective equipment, field to the needs of field inspection.You can al雷竞技appso use the accompanying Fluke Energy Analyze Plus package, easily draw diagrams for measuring results, help identify problems and create a detailed report.As selective function, you can also create IEEE519 report, in order to further understand the level of harmonic, voltage/current distortion and load current () need to be licensed.
Other useful functions:
- In th雷竞技appe recorder, Fluke Connect mobile applications and desktop software, or by your wi-fi infrastructure facilities to provide the data.
- Use the attached four flexible all three phase line and neutral line current probe measurements
- Directly from the measuring instrument circuit for power supply
- During the recording session, and check the measurements before download, for real-time analysis
- Included in the 1738 incident wave snapshots and high resolution true RMS configuration files, as well as the date and time stamp and seriousness to capture sag, temporary rise and surge current, and help find out the underlying cause of the power quality problems
- 1738 by power quality health shall also provide quick reference about electrical system overall health
- Bright color touch screen, which the scene analysis and data check
- Through rapid facilitated the graphical user interface, to help you always capture the correct data
- Through intelligent validation functions to reduce uncertainty in connection
- Allows you to thr雷竞技appough the front panel or a smart phone Fluke Connect application field Settings
- With oth雷竞技apper support Fluke Connect completely integrated logging equipment, so that the Fluke Connect wireless digital multimeter, or module on * record up to two additional parameters at the same time
- The attached Energy Analyze Plus application software, enables you to Analyze Energy consumption and power quality and create the health of every detail report automatically
Records of the most common parameters
1736 and 1738 models are designed to measure the key of three-phase electric energy parameters, can also record the RMS voltage, RMS current, voltage and current events, THD, as much as 50 times harmonic voltage and current harmonic voltage and current, active power, reactive power, power factor, active power, reactive power, etc.1736 and 1738 models have enough storage space, data record for more than a year, can find missing or hard to find.
Analysis and reporting
Access to data is only part of the job.After you get the data, you need to create useful information and reports, let your organization or the customer can easily share and understand.雷竞技appFluke Energy Analyze Plus software for such a job change numerous for brief.Through the analysis of powerful tools, a few minutes to create a custom report, found that you can notice the results and quickly solve the problem, which can optimize system reliability and save money.
Produc雷竞技appt specifications: Fluke three-phase power quality recorder instrument for 1736 and 1738
Technical indicators | |||||
precision | |||||
parameter | range | The resolution of the | Under the condition of the reference of the basic accuracy + full scale percentage percentage (reading) | ||
voltage | 1000 V | 0.1 V | Plus or minus (0.2% + 0.01%) | ||
Current: direct current input | I17xx - flex 1500 12" | 150 A | 0.1 A | Plus or minus (1% + 0.02%) | |
1500 A | 1 A | Plus or minus (1% + 0.02%) | |||
I17xx - flex 3000 24" | 300 A | 1 A | Plus or minus (1% + 0.03%) | ||
3000 A | 10 A | Plus or minus (1% + 0.03%) | |||
I17xx - flex 6000 36" | 600 A | 1 A | Plus or minus (1.5% + 0.03%) | ||
6000 A | 10 A | Plus or minus (1.5% + 0.03%) | |||
I40s - EL current clamp | 4 A | 1 mA | Plus or minus (0.7% + 0.02%) | ||
40 A | 10 mA, | Plus or minus (0.7% + 0.02%) | |||
frequency | 42.5 Hz - 69 Hz | 0.01 Hz | Plus or minus (0.1%) | ||
Auxiliary input | Plus or minus 10 V dc | 0.1 mV | Plus or minus (0.2% + 0.02%) | ||
Minimum/maximum voltage | 1000 V | 0.1 V | Plus or minus (1% + 0.1%) | ||
The current minimum/maximum | Determined by the current probe | Determined by the current probe | Plus or minus (5% + 0.2%) | ||
Voltage THD | 1000% | 0.1% | + / - 0.5 | ||
Current THD | 1000% | 0.1% | + / - 0.5 | ||
2 to 50 times the voltage harmonic | 1000 V | 0.1 V | P V: reading plus or minus 5% | ||
< 10 V: + / - 0.5 V | |||||
2 to 50 current harmonic | Determined by the current probe | Determined by the current probe | Current range of 3% or higher: reading plus or minus 5% | ||
< 3% of the current range: the range of + / - 0.15% | |||||
Unbalance (imbalances) | 100% | 0.1% | + / - 0.2 | ||
The inherent uncertainty + + percentage range percentage (reading) creates | |||||
parameter | Amount of influence | IFlex1500-12 | IFlex3000-24 | IFlex6000-36 | I40S - EL |
150 A / 1500 A | 300 A / 3000 A | 600 A / 6000 A | 4 A / 40 A | ||
Active power P | PF acuity 0.99 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
Active energy Ea. | PF acuity 0.99 | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
Apparent power S | 0 or less PF 1 or less | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
The apparent energy Eap | 0 or less PF 1 or less | 1.2% + 0.005% | 1.2% + 0.0075% | 1.7% + 0.0075% | 1.2% + 0.005% |
Reactive power Q | 0 or less PF 1 or less | Has 2.5% of the measurement of apparent power | |||
E has no functionr | 0 or less PF 1 or less | Has 2.5% of the measurement of apparent power | |||
Power factor PF | - | + / - 0.025 | |||
The displacement power factor | - | + / - 0.025 | |||
DBF/cos ϕ | - | + / - 0.025 | |||
Range creates additional uncertainty | VP - N> 250 V | 0.015% | 0.0225% | 0.0225% | 0.015% |
Creates range Irange = 1000 V x Reference conditions:
|
Electrical technical indicators | |
The power supply | |
Voltage range | Use safety input plug by measuring circuit for 100 V to 500 V power supply |
When using the standard power cord for 100 V to 240 V (IEC 60320 C7) | |
Power consumption | Maximum 50 VA (using IEC 60320 input when the maximum is 15 VA) |
The efficiency of | 68.2% or greater (conform to the specifications of energy efficiency) |
Maximum no-load loss | < 0.3 W (only when using IEC 60320 input) |
The main power supply frequency | 50/60 Hz plus or minus 15% |
The battery | Lithium ion battery 3.7 V, 9.25 Wh (customer can be replaced) |
Battery run time | Standard operation mode for four hours, up to 5.5 hours power saving mode |
Charging time | The < 6 hours |
The data collection | |
The resolution of the | A 16-bit synchronous sampling |
Sampling frequency | When 50/60 Hz to 10.24 kHz, with power frequency synchronization |
The input signal frequency | 50/60 Hz (42.5 to 69 Hz) |
Connection mode type | 1 - phi, 1 - phi IT, split phase, 3 - phi delta, 3 - phi wye, 3 - phi wye IT, 3 - phi wye balance, 3 - phi Aron/Blondel (two table method), 3 - phi delta open foot, only current (load analysis) |
Data is stored | Internal flash memory (the user can't change) |
Memory capacity | Typical values: 10 for 8 weeks, interval recording session for 1 minute and 500 event creates |
Creates may record the session number and cycle depends on the user's needs. | |
Basic interval | |
The parameters of the measurement | Voltage, current, Aux, THD, frequency, THD V A, power, power factor, the fundamental wave power, DPF, electric energy |
The average interval | Users can choose: 1 second, 5 seconds, 10 seconds, 30 seconds, 1 minute, 5 minutes, 10 minutes, 15 minutes, 30 minutes |
The average time minimum/maximum | The RMS voltage, current, complete cycle update every half cycle (URMS1/2 meet IEC61000-4-30 Aux, power: 200 ms |
Demand interval (energy meter mode) | |
The parameters of the measurement | Electrical energy (Wh, varh, VAh), PF, maximum demand, electricity costs |
interval | User optional: 5 minutes, 10 minutes, 15 minutes, 20 minutes, 30 minutes, shut |
Power quality measurement | |
The parameters of the measurement | Voltage, frequency, unbalance, voltage, current harmonic, harmonic and THD V THD A and TDD |
The average interval | 10 min (mv) |
Every harmonic | 2 to 50 harmonics |
Total harmonic distortion | Calculated at 50 harmonics |
The event | : voltage sag, temporarily litres, interruption, electric current, the surge current |
Trigger records | Update every half cycle of the whole frequency voltage and current RMS (Urms1/2 meet IEC61000-4-30) |
The voltage and current waveform (1738). | |
Conform to the standard | |
harmonic | IEC 61000-4-7:1 |
The IEEE 519 (short time harmonic) | |
The power quality | IEC 61000-4-30 S level, IEC62586-1 (PQI - S equipment) |
The power supply | The IEEE 1459 |
Power quality compliance | EN50160 (used to measure parameters) |
interface | |
USB - A | Through the USB flash drives for file transfer, the firmware update Maximum current: 120 mA |
WiFi | Through the direct connection or WiFi network file transfer and remote control |
bluetooth | Fr雷竞技appom Fluke Connect ® 3000 series modules read aided measurement data (1738 or 1736 upgrade option) |
USB to mini | Download the data to the PC |
The input voltage | |
Enter the number of | Four (three phase and zero line) |
Maximum input voltage | 1000 Vrms, CF 1.7 |
The input impedance | 10 M Ω |
Bandwidth (3 dB) | 42.5 Hz to 3.5 kHz |
The zoom | 1:1, variable |
Measurement category | The CAT CAT III 1000 V / 600 V IV |
Current input | |
Enter the number of | 4, automatically select sensors connected mode |
The input voltage | Current clamp type: 500 mVrms / 50 mVrms;CF 2.8 |
Rogowski coil of roche input | When 50 Hz 150 mVrms / 15 mVrms, 60 Hz to 180 mVrms / 18 mVrms;Crest factor 4;All in the probe is rated range |
range | Using thin flexible current probe i17XX - flex1500 12 "1 A - 150 - A / 10 A to 1500 A |
Using thin flexible current probe i17XX - flex3000 24 "for 30 A to 3 A to 300 A / 3000 A | |
Using thin flexible current probe i17XX - flex6000 36 "for the 6 A - 600 - A/A 60 to 6000 A | |
40 mA to 4 A / 0.4 A and 40 A (40 A current clamp i40s - EL) | |
Bandwidth (3 dB) | 42.5 Hz to 3.5 kHz |
The zoom | 1:1, variable |
Auxiliary input | |
Enter the number of | 2 |
The input range | 1 to 0 to + 10 V dc, readings per second |
The scale factor | Format: mx + b (gain and offset) user configurable |
According to the unit | Users can configure (seven characters, such as ° C, psi or m/s) |
A wireless connection | |
Enter the number of | 2 |
Supported by the module | 雷竞技appFluke Connect ® 3000 series |
collect | 1 readings per second |
Environmental parameters | |
Working temperature | - 10 ° C to + 50 ° C (14 ° F to 122 ° F) |
Storage temperature | - 20 ° C to + 60 ° C (4 ° F to 140 ° F), including battery: - 20 ° C to + 50 ° C (4 ° F to 122 ° F) |
Working humidity | 10 ° to 30 ° C C (50 ° F to 86 ° F) maximum relative humidity of 95% |
30 ° C to 40 ° C (86 ° F to 104 ° F) maximum 75% relative humidity | |
40 ° C to 50 ° C (104 ° F to 122 ° F) maximum 45% relative humidity | |
Work at an altitude of | 2000 m (up to 4000 m when reduced to 1000 V / 600 V II CAT CAT CAT III / 300 V IV) |
For altitude | 12000 m |
The shell | IP50 (meet EN60529) |
vibration | MIL - T - 28800 - e, type 3, level III, B type |
security | IEC 61010-1 |
The IEC power input: overvoltage category II, pollution level 2 | |
Voltage terminal: overvoltage category IV, pollution level 2 | |
IEC 61010-2-031: the CAT III 1000 V, 600 V/CAT IV | |
Electromagnetic compatibility | EN 61326-1: industrial CISPR 11: group 1, class A |
South Korea (KCC) : class A equipment (industrial radio and communication equipment) | |
The United States (FCC) : 47 CFR part 15 B.According to the provisions of article 15.103 of this product is regarded as tax-free equipment | |
The temperature coefficient of | Precision index x / 0.1 ° C |
General technical indicators | |
Color LCD display | 4.3 inch TFT active matrix, 480 x 272 pixels pixels, resistive touch screens |
The warranty period | Instruments and power supply: two years (not including battery) |
Accessories: one year | |
Calibration period: two years | |
size | Instruments: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in) |
Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in) | |
Instruments (with power supply) : 19.8 cm x 16.7 cm x 9 cm (7.8 in x 6.6 in x 3.5 in) | |
The weight of the | Instruments: 1.1 kg (2.5 lb) |
Power supply: 400 g (0.9 lb) | |
Tamper-proof protection | Anti-theft lock slot |
I17xx - flex 1500 12 "flexible current probe technical indicators | |
Measuring range | 1-150 - A 10-1500 - A ac alternating current (ac) / |
Current nondestructive | 100 kA (50/60 Hz) |
The inherent error * reference conditions | Readings of plus or minus 0.7% |
173 x + iFlex accuracy | Plus or minus (1% + 0.02% range readings) |
Beyond the working temperature range of temperature coefficient | 0.05% of the readings / ° C, 0.09% of the readings / ° F |
Working voltage | The CAT CAT III 1000 V, 600 V IV |
The probe cable length | 305 mm (12 in) |
The probe cable diameter | 7.5 mm (0.3 in) |
The minimum bending radius | 38 mm (1.5 in) |
The output cable length | 2 m (6.6 ft) |
The weight of the | 115 g |
The probe cable material | TPR |
Connector material | POM + ABS/PC |
The output cable | TPR/PVC |
Working temperature | Test environment conductor temperature was minus 20 ° C to + 70 ° C (4 ° F to 158 ° F), does not exceed 80 ° C (176 ° F) |
Non-work state temperature | To 40 ° C to + 80 ° C (to 40 ° F to 176 ° F) |
The working status of relative humidity | Between 15% and 85% with no condensation |
The IP rating | IEC 60529: IP50 |
The warranty period | 1 year |
* reference conditions:
|
Mode雷竞技appl: Fluke three-phase power quality recorder instrument for 1736 and 1738
Portable high power quality recorder (not including current probe)
Include:
- 雷竞技appFluke 1738 instrument
- Voltage test lead group
- Alligator clip (4 x)
- Soft, portable package
- Energy Analyze Plus software
- The power cord
- Color code group
Portable high power quality recorder Europe/us models
Include:
- 雷竞技appFluke 1738 instrument
- Voltage test lead group
- Alligator clip (4 x)
- 12 inches 1500 A flexible current probe (4 x)
- Soft, portable package
- Energy Analyze Plus software
- Wi-fi adapter
- Bluetooth adapter
- The power cord
- Color code group
Portable high power quality recorder international version
Include:
- 雷竞技appFluke 1738 instrument
- Voltage test lead group
- Alligator clip (4 x)
- 12 inches 1500 A flexible current probe (4 x)
- Soft, portable package
- Energy Analyze Plus software
- The power cord
- Color code group
Portable power quality recorder (not including current probe)
Include:
- 雷竞技appFluke 1736 instrument
- Voltage test lead group
- Alligator clip (4 x)
- Soft, portable package
- Energy Analyze Plus software
- The power cord
- Color code group
Portable power quality recorder Europe/us models
Include:
- 雷竞技appFluke 1736 instrument
- Voltage test lead group
- Alligator clip (4 x)
- 12 inches 1500 A flexible current probe (4 x)
- Soft, portable package
- Energy Analyze Plus software
- Wi-fi adapter
- Bluetooth adapter
- The power cord
- Color code group
Portable power quality recorder international version
Include:
- 雷竞技appFluke 1736 instrument
- Voltage test lead group
- Alligator clip (4 x)
- 12 inches 1500 A flexible current probe (4 x)
- Soft, portable package
- Energy Analyze Plus software
- The power cord
- Color code group
Manual + 雷竞技appresources: Fluke three-phase power quality recorder instrument for 1736 and 1738
- Using fluke electrical energy recorder for 30 days load analysis related guidelines
- Measuring power quality needs to be done before 6
- Monitor the power to create four unique opportunity | application cases
- Load study six mistakes often | application cases
- Need to record the electric energy and electricity five reasons why | application cases
- Functions and characteristics of F1736/1738 is introduced
- F1736/1738 software function is introduced
- F17361738 features and applications - equipment maintenance and troubleshooting
- Android wifi and VNC APP Settings F173X and view the data
- Power quality | application case 2
- Power quality | application case 3
- Power quality | application case 4