China

雷竞技appFluke 434-2 and 435 - II power quality and energy analyzer

  • 雷竞技appThe Fluke 435 Series II Power Quality and Energy Analyzer front view
  • 雷竞技appThe Fluke 435 Series II Power Quality and Energy Analyzer
  • 雷竞技appThe Fluke 434-2 and 435 - II Power Quality and Energy Analyzers
  • 雷竞技appThe Fluke 434-2 and 435 - II Power Quality and Energy Analyzers

The main features

Use雷竞技app the Fluke 434 - II energy analyzer and the Fluke 435 - II power quality and energy analyzer to analyze the power quality problems, to calculate the cost of electrical energy waste and preventing downtime.

  • Advanced power quality health -To obtain real-time overview of the health status of power quality, so you can make better maintenance decisions
  • Energy loss calculator -Found that the energy loss due to poor power quality cost
  • The high level of security -1000 V / 600 V IV CAT CAT III

Produc雷竞技appts overview: Fluke 434-2 and 435 - II power quality and energy analyzer

Suggestions to the fluke official flagship store of purchase

雷竞技appFluke 434-2 and 435 - II power quality analyzer is designed to help you to a greater extent to shorten downtime, quickly eliminate the power quality problems, and easily found waste electricity costs.Stop the opportunity to produce high price, and quick access to the data is the key to solve the problem of critical power supply quality.The 434-2 and 435 - II分析仪的测量过程和数据输出已经过优化,可以帮助您轻松了解到关键信息。

Measurement is presented according to the format, multiple parameters describing the overall power quality health quickly.Whether you want to try to reduce energy waste, power quality and find the root cause, or want to check the motor start to you the influence of the electric system, detailed data can help you make better maintenance decisions.Data can be used as a simple numerical, trend chart (in order to quickly understand the changes over time), waveform or phasor diagram for storage.Data can also be analyzed and exported as a table format.Detailed event data enables you to view the fault level, duration and time node, enabling you to quickly related problems arising in the course of your facilities.

Energy loss calculator -Because of the amount of energy waste and loss calculation.

雷竞技appThe Fluke 430 series II energy loss calculator
雷竞技appThe Fluke 430 series II energy loss calculator

There is no doubt that the power of the poor quality may produce significant impact on profits.雷竞技appThe Fluke 434 - II和 Fluke 435-II 电能质量分析仪使您能够确定问题和衡量能量损失,让您具体地了解损失金额。通过在有效功率和不良电能质量特征(如无功功率、不平衡、失真或中性线电流)之间建立关联,能量损耗计算器可帮助您更好地理解自己的能耗。这些电能质量和能量分析仪还为用户提供灵活性,让他们可以输入电缆长度和直径来计算由于导体大小调整而引起的损耗(如果电缆规格未知,则使用自动模式),并可以输入最多四个随时间变化的唯一日费率 (kWh) 以进行更准确的计算。有了这些重要数据,用户就可以轻松证明为采取对策而必需的投资是合理的。

Advanced power quality health- real-time power quality health overview, so that when you need to provide the required data

Powerwave data capture
Powerwave data capture

雷竞技appThe Fluke 434-2 and 435 - II power quality and energy analysis using integrated power quality health profile, real-time to provide you with comprehensive overview of power quality problem.Through a simple graphical display and the limit deviation, you can quickly find the electrical system of the power quality problems.If you don't know where to start, or there may be a problem, you can use advanced health profile is to simplify the task of power quality, and as a further comprehensive starting point for troubleshooting.

Power inverter efficiency

Power inverter is responsible for direct current into alternating current or alternating current into direct current.However, into the part of the power inverter in what proportion as the output current?雷竞技appThe Fluke 434 - II和 435-II 分析仪具有集成的电力逆变器效率模式,可以帮助用户更好地了解电力逆变器性能。没有哪种逆变器的效率能达到 100%,电力逆变器的效率会根据当时所使用的电力多少而有所不同(当使用的电力较多时,效率通常会更高)。逆变器的性能也会随时间而降低,需定期检查。通过比较输入和输出功率,可以得知系统效率。利用电力逆变器效率功能,您可以发现逆变器在将直流电转换为交流电(或反之)方面的表现。

AutoTrend -Quick view the trend

AutoTrend function can show changes over time
AutoTrend function can show changes over time

Use of unique AutoTrend function, you can quickly understand the power quality changes over time.It automatically and continuously records show that every reading, without having to set the level threshold or manual start-up process, so you can quickly see all the three phase line and neutral line voltage, current, frequency, power, harmonic and flicker.

Advanced power quality function, analysis of unprecedented power performance

Power quality problems may affect the operation of the critical load, and a very bad impact on your profits.Th雷竞技appe Fluke 435 - II power quality and power analyzer for your insurance policy.Calculating electric energy wasted due to poor power quality costs and eliminate the root cause of the power quality and motor performance problems, all of which use a simple test tools, the tool will provide you with the data required to quickly find the root cause.

雷竞技appFluke and 435-434 - II power analyzer II power quality and power analyzer in a lightweight solid shell, is an ideal portable power quality analysis instrument.

  • Quick look for electric energy waste and the amount of loss (in dollars) for the unit.
  • To obtain real-time overview of the health status of power quality, so you can make better maintenance decisions
  • Use the attached flexible all three phase line and neutral line current probe measurements
  • Easy to understand how to influence the electrical motor start performance of the system
  • Security level: introducing safety CAT CAT IV standard 600 V / 1000 V III
  • Com雷竞技apppatible with Fluke Connect ® * - by instruments to check the data locally, by Fluke Connect mobile applications and PowerLog 430 - II desktop software to check the data

雷竞技appFluke 430 - II series power quality analyzer

雷竞技appFluke 434 - II power analyzer can help you understand the overall energy usage, consumption of electricity and for your facility.雷竞技appThe Fluke 435 - IIThe power quality和电能分析仪具有与 434-II 相同的出色功能,另外还增加了高级电能质量功能,以便进行更深入的故障排除。如果您需要与 435-II 相同的高级功能,可使用更高频率的 Fluke 437-II 型号,该型号是适合 400 Hz 电力系统的必备电能质量分析仪。最后,Fluke 438-II 电能质量和电机分析仪具有 Fluke 435-II 的所有电能质量和电能分析功能,而且可以在无需机械传感器的情况下测量电机机械参数,例如电机速度、扭矩和机械功率。

function 雷竞技appThe Fluke 434 - II 雷竞技appThe Fluke 435 - II 雷竞技appThe Fluke 437 - II 雷竞技appThe Fluke 438 - II
Power measurement
Power quality measurement
Accord with the standard IEC61000-4-30 S class Class A Class A Class A
Power, power loss and calculator
Monitoring and trend analysis
Surge, inverter efficiency
Advanced analysis;The incident wave, flicker, transient, electric signal and electric waves
Marine power and 400 hz
The motor electrical and mechanical analysis (optional) (optional) (optional)
SD card

Produc雷竞技appt specifications: Fluke 434-2 and 435 - II power quality and energy analyzer

voltage
model range The resolution of the precision
Vrms (ac + dc) 434 - II 1 V to 1000 V voltage 0.1 V Plus or minus 0.1% rated voltage1
435 - II 1 V to 1000 V voltage 0.01 V Plus or minus 0.1% rated voltage1
Vpk 1 Vpk Vpk to 1400 1 V 5% of the nominal voltage
Voltage peak factor (CF) 1.0 > 2.8 0.01 Plus or minus 5%
Vrms 1/2 level 434 - II 1 V to 1000 V voltage 0.1 V Plus or minus 1% rated voltage
The 434-2 and 435 - II 0.1 V Plus or minus 0.2% rated voltage
Vfund 434 - II 1 V to 1000 V voltage 0.1 V Plus or minus 0.5% rated voltage
435 - II 0.1 V Plus or minus 0.1% rated voltage
Current (not including current clamp precision accuracy)
+ dc current (ac) I430 - Flex 1 x 5 A to 6000 A 1 A Plus or minus 0.5% plus or minus five count
I430 - Flex 10 x 0.5 A to 600 A 0.1 A Plus or minus 0.5% plus or minus five count
1 mv/A 1 x 5 A to 2000 A 1 a Plus or minus 0.5% plus or minus five count
1 mv/A 10 x 0.5 A - 200 - A (alternating current) only 0.1 A Plus or minus 0.5% plus or minus five count
Apk I430 - Flex 8400 Apk 1 very different Plus or minus 5%
1 mv/A 5500 Apk 1 very different Plus or minus 5%
Current crest factor (CF) 1 to 10 0.01 Plus or minus 5%
Amps 1/2 level I430 - Flex 1 x 5 A to 6000 A 1 A Plus or minus 1% plus or minus 10 counts
I430 - Flex 10 x 0.5 A to 600 A 0.1 A Plus or minus 1% plus or minus 10 counts
1 mv/A 1 x 5 A to 2000 A 1 A Plus or minus 1% plus or minus 10 counts
1 mv/A 10 x 0.5 A - 200 - A (alternating current) only 0.1 A Plus or minus 1% plus or minus 10 counts
Afund I430 - Flex 1 x 5 A to 6000 A 1 A Plus or minus 0.5% plus or minus five count
I430 - Flex 10 x 0.5 A to 600 A 0.1 A Plus or minus 0.5% plus or minus five count
1 mv/A 1 x 5 A to 2000 A 1 A Plus or minus 0.5% plus or minus five count
1 mv/A 10 x 0.5 A - 200 - A (alternating current) only 0.1 A Plus or minus 0.5% plus or minus five count
Hz
Hz 雷竞技appFluke 434 @ rated frequency 50 Hz 42.50 Hz to 57.50 Hz 0.01 Hz + / - 0.01 Hz
雷竞技appFluke 434 @ rated frequency of 60 Hz 51.00 Hz to 69.00 Hz 0.01 Hz + / - 0.01 Hz
雷竞技appFluke 435 @ rated frequency 50 Hz 42.500 Hz to 57.500 Hz 0.001 Hz + / - 0.01 Hz
雷竞技appFluke 435 @ rated frequency of 60 Hz 51.00 Hz to 69.00 Hz 0.001 Hz + / - 0.01 Hz
The power supply
Watt (VA, var) I430 - Flex The largest of 6000 MW 0.1 W to 1 MW Plus or minus 1% plus or minus 10 counts
1 mV/A The largest of 2000 MW 0.1 W to 1 MW Plus or minus 1% plus or minus 10 counts
J/DPF power factor (Cos) 0 to 1, 0.001 Plus or minus 0.1% @ rated load conditions
energy
KWh (kVAh, kvarh) I430 - Flex 10 x Depending on the current clamp variable ratio and the rated voltage Plus or minus 1% plus or minus 10 counts
Energy loss I430 - Flex 10 x Depending on the current clamp variable ratio and the rated voltage Plus or minus 1% plus or minus 10 counts do not contain line resistance precision
harmonic
The harmonic number (n) Dc, 1 to 50 times group: harmonic grouping, according to IEC 61000-4-7
Between the harmonic number (n) Shut down, 1 to 50 times group: between harmonic and harmonic subgroups, according to IEC 61000-4-7
Voltage % f (0.0% to 100%) 0.1% Plus or minus 0.1% + n x 0.1%
r (0.0% to 100%) 0.1% Plus or minus 0.1% + n x 0.4%
The absolute threshold 0.0 to 1000 V 0.1 V Plus or minus 5%1
THD (0.0% to 100%) 0.1% Plus or minus 2.5%
Current % f (0.0% to 100%) 0.1% Plus or minus 0.1% + n x 0.1%
r (0.0% to 100%) 0.1% Plus or minus 0.1% + n x 0.4%
The absolute threshold 0.0 to 600 A 0.1 A Plus or minus 5% plus or minus five count
THD (0.0% to 100%) 0.1% Plus or minus 2.5%
Power % F or r (0.0% to 100%) 0.1% + n x 2%
The absolute threshold Depending on the current clamp variable ratio and the rated voltage - Plus or minus 5% + n x 2% plus or minus 10 counts
THD (0.0% to 100%) 0.1% Plus or minus 5%
Phase Angle - 360 ° to + 0 ° 1 ° + n x 1 °
flicker
Plt, Pst, Pst Pinst (1 minute) 0.00 to 20.00 0.01 Plus or minus 5%
Unbalance (imbalance)
Voltage % (0.0% to 20.0%) 0.1% Plus or minus 0.1%
Current % (0.0% to 20.0%) 0.1% Plus or minus 1%
The power signal
The threshold level Under the two independent frequency, threshold, limit, and the duration of the programmable control signal - -
Signal frequency 60 Hz and 3000 Hz 0.1 Hz
The relative V % (0% to 100%) 0.10% Plus or minus 0.4%
Average absolute threshold V3s (3 seconds) 0.0 V to 1000 V 0.1 V Plus or minus 5% rated voltage
General technical indicators
The shell With one-piece protective holster design solid and shockproof, used to tilt the upright position, with IEC60529 IP51 level dust-proof waterproof drops hit 30 g to withstand the impact and vibration, vibration level: in accordance with MIL - PRF - 28800 - f grade 2 for 3 g sine, random vibration of 0.03 g / 2 Hz
display Brightness: 200 CD/m2 (generally use the power adapter).90 CD/m2 (generally) using battery power of 127 x 88 mm (153 mm / 6.0 diagonal) LCD resolution: 320 x 240 pixels contrast and brightness: user adjustable, with temperature compensation
memory 8 gb SD card (conform to the requirements of the SDHC, FAT32 format), the largest optional 32 gb.Screen saving and multiple data memory used to store all kinds of data including records (depending on memory size).
Real time clock For trend model, transient display and system monitoring and event capture time and date are identified
Environmental requirements
Working temperature 0 ° C ~ + 40 ° C;40 ° C ~ + + 50 ° C battery
Storage temperature - 20 ° C ~ + 60 ° C
humidity + 10 ° C ~ + 30 ° C: 95% relative humidity and condensation
+ 30 ° C ~ + 40 ° C: 75% relative humidity and condensation
40 ° C ~ + + 50 ° C: 45% relative humidity and condensation
Maximum working altitude The fourth class 600 V (IV), the third class (CAT III) 1000 V, up to an altitude of 2000 meters (6666 feet)
The third class (CAT III) 600 V, the second type (CAT) II 1000 V, the supreme to an altitude of 3000 meters (10000 feet)
Highest storage height of 12000 meters (40000 feet)
Electromagnetic compatibility (EMC) Radiation and anti-jamming in accordance with EN 61326 (2005-12)
interface Mini USB - type B isolation USB ports, used to connect to PC SD connect card slot (can be accessed from the back of the battery instrument)
The warranty period Host three years warranty (parts and labor), the attachment is one year warranty
See the full series of specifications »
1. If greater than or equal to 1% of rated voltage, the plus or minus 5%;If less than 1% rated voltage, the plus or minus 0.05%
2. According to IEC 61000-4-30, rated frequency 50 hz / 60 hz
3. The flicker, power lines and monitoring mode does not support 400 hz measured values
4. The rated voltage of 50 V to 500 V

Mode雷竞技appl: Fluke 434-2 and 435 - II power quality and energy analyzer

雷竞技appThe Fluke 435 - II
Three-phase power quality and energy analyzer

The attached:

  • BC430 power adapter
  • International plug adapter kit
  • BP290 (single lithium ion batteries), 28 wh 8 hours (or longer)
  • TLS430 test wires and alligator clip suite
  • WC100 color BianMaGa and regional tag stickers
  • I430 - Flexi - TF - II, 24 inches (61 centimeters) long, four flexible current probe
  • 8 gb SD card
  • PowerLog CD (including operator manual in PDF format)
  • A - the Mini B USB cable
  • Portable soft package
雷竞技appThe Fluke 434 - II

Three-phase electric energy analyzer

The attached:

  • BC430 power adapter
  • International plug adapter kit
  • BP290 (single lithium ion batteries), 28 wh 8 hours (or longer)
  • TLS430 test wires and alligator clip suite
  • WC100 color BianMaGa and regional tag stickers
  • I430flex - TF, 24 inches (61 centimeters) long, four flexible current probe
  • 8 gb SD card
  • PowerLog CD (including operator manual in PDF format)
  • A - the Mini B USB cable
  • C1740 soft package
雷竞技appThe Fluke 435 series II Basic
雷竞技appFluke 435 series II Basic three-phase power quality and energy analyzer

The attached:

  • BC430 power adapter
  • International plug adapter kit
  • BP290 (single lithium ion batteries), 28 wh 8 hours (or longer)
  • TLS430 test wires and alligator clip suite
  • WC100 color BianMaGa and regional tag stickers
  • 8 gb SD card
  • PowerLog CD (including operator manual in PDF format)
  • A - the Mini B USB cable
雷竞技appFluke 434 - II Basic
雷竞技appFluke 434 series II Basic electric energy analyzer

The attached:

  • BC430 power adapter
  • International plug adapter kit
  • BP290 (single lithium ion batteries), 28 wh 8 hours (or longer)
  • TLS430 test wires and alligator clip suite
  • WC100 color BianMaGa and regional tag stickers
  • 8 gb SD card
  • PowerLog CD (including operator manual in PDF format)
  • A - the Mini B USB cable
  • C1740 soft package
雷竞技appThe Fluke 430 - II motor analyzer upgrade kit

430 - II motor analyzer upgrade kit

Include:

  • Firmware upg雷竞技apprade package, for the existing Fluke 434, 435 and 437 series II power quality analyzer increase motor analysis function

Manual + 雷竞技appresources: Fluke 434-2 and 435 - II power quality and energy analyzer