China

雷竞技appFluke i430 Flex ac current probe

  • 雷竞技appFluke i430 Flex Current Clamp

Produc雷竞技appts overview: Fluke i430 Flex ac current probe

I430 Flex is a Rogowski principle of ac current probe.Flexible light measuring head allows the user to quickly and easily installed in the area of remoteness, without using the battery or external power supply.

I430 current clamp table using 4 pieces type packaging, can be used in high current measurement.Flex clamp table joins in bus and large size wire or hard to get around the conductor.4 piece in cur雷竞技apprent clamp table is especially suitable for and Fluke 430 series three-phase tools such as supporting the use.

Produc雷竞技appt specifications: Fluke i430 Flex ac current probe

General technical specifications
Probe and cable material TPE rubber, reinforced insulation
UL94 V - 0, color: red Munsell 7.5
R 1/14
Joint material Polypropylene, UL94 V - 0
The probe cable length 610 mm
The probe cable diameter The 12.4 mm
The probe cable bending radius 40 mm
The output cable length 2.5 m RG58
Output connector Security BNC connector
The scope of work - 20 - to + 90 ° C
Storage temperature - 40 to + 105 ° C
Working humidity From 15% to 85% (condensate)
Protection grade (probe) IP41
Technical specifications
Current range 3000 A ac RMS
The output voltage (1000 A RMS, 50 Hz) 85 mV
precision Readings of plus or minus 1%
(@ 25 ° C, 50 Hz)
Linearity (range 10% to 100%) Readings of plus or minus 0.2%
Noise (10 Hz - 7 kHz) 1.0 mV ac RMS
Output impedance Minimum 82 Ω
The load impedance 50 k Ω
Each internal resistance of the probe length of 100 mm 10.5 Ω plus or minus 5%
Width (3 db) 10 Hz to 7 kHz
Phase error (45-65 Hz) Plus or minus 1 °
Position the sensitivity Maximum plus or minus 2% of reading
The temperature coefficient of The biggest readings of plus or minus 0.08% / ° C
Working voltage (see section "safety standard") 1000 V AC RMS or DC (measurement)
A maximum of 30 V.(output)
Safety specifications
Safety standards BS EN 61010-1 2001
BS EN 61010-2-032-2002
BS EN 61010-031, 2002100 VRMS, class III, the pollution level 2
Using probe on uninsulated conductor is limited to 1000 V ac RMS or dc, and the frequency of 1 KHZ.
Please note that the p雷竞技approbes are used together with other products, suitable for and the Fluke 435 systems
Output terminal earthing safety level limit of 600 V AC RMS or DC.

Mode雷竞技appl: Fluke i430 Flex ac current probe

雷竞技appFluke i430